Gilbert hazardous materials reporting, and the site map that goes with it.
The Town of Gilbert makes businesses report hazardous materials at quantities far below the state’s Tier II thresholds, through the same state filing system. That system now requires a site map with every Tier II report. RevealBuilt is based in Gilbert and draws them.
Who has to file in Gilbert
Gilbert Fire Prevention Regulation 18-5003.4.1 (2018 International Fire Code, amended Section 5003.4.1, revised 3/6/2024) requires a new or existing business to file electronically when it possesses or stores more than any of these, per individual chemical:
| Form | Gilbert threshold | State Tier II threshold |
|---|---|---|
| Liquid | 55 gallons | 10,000 pounds for most hazardous chemicals. 500 pounds or the threshold planning quantity, whichever is lower, for extremely hazardous substances. |
| Gas | 200 cubic feet | |
| Solid | 500 pounds | |
| Aerosols | 2,500 pounds |
- The thresholds are not combined. In the regulation’s own example, 75 cubic feet of acetylene and 300 cubic feet of carbon monoxide means only the carbon monoxide is reported.
- Every Group H occupancy files, whatever the quantity.
- The fire code official may require more: an approved hazardous materials management plan (HMMP), and, where community health and safety call for it, a filing and a facility emergency response plan from any business.
- File by chemical name, not product name.
Where the site map comes in
Gilbert uses the State of Arizona’s Tier II system for all of this filing. ADEQ states that a site map is now mandatory for every facility submitting a Tier II report in that system, and lists what it must show: all points of ingress and egress, where substances are stored in and around the facility, and the general layout.
Gilbert’s regulation does not describe a site map of its own. Where the fire code official requires an HMMP, the International Fire Code (Section 5001.5.1) calls for a facility site plan that shows more: access to each storage and use area, emergency equipment, where responders meet your liaison, evacuation meeting points, tanks and their piping, the hazard classes in each area, control areas and Group H areas, and emergency exits. We draw to either list. Ask Gilbert Fire Prevention which one applies to you before you order.
RevealBuilt is a Gilbert company. A measured site map ready for upload is $500 plus $0.05 per square foot scanned, with no travel charge anywhere in Gilbert. Yearly update $150. A map drawn to the fuller HMMP list is quoted by the site.
What are Gilbert’s hazardous materials reporting thresholds?
Gilbert Fire Prevention Regulation 18-5003.4.1 requires electronic filing for any business holding more than 55 gallons of a liquid, 200 cubic feet of a gas, 500 pounds of a solid or 2,500 pounds of aerosols. Each threshold applies to an individual chemical, not to the combined total.
How is that different from the state Tier II thresholds?
The state thresholds are 10,000 pounds for most hazardous chemicals and 500 pounds or the threshold planning quantity, whichever is lower, for extremely hazardous substances. Gilbert’s triggers are much lower, so a business can owe Gilbert a filing without owing the state a Tier II report.
Where do Gilbert businesses file?
In the State of Arizona’s Tier II system, which ADEQ runs in its myDEQ portal. Gilbert uses it for all electronic filing, tracking and reporting.
Does a Gilbert-only filer pay the state Tier II fee?
ADEQ states that facilities reporting only chemicals that meet the Gilbert regulation are exempt from the state’s Tier II filing fees.
Does a Gilbert filing need a site map?
Gilbert’s regulation does not mention a site map. The requirement comes from the filing system: ADEQ states a site map is mandatory for all facilities submitting Tier II reports in myDEQ. Confirm with Gilbert Fire Prevention how that applies to a Gilbert-only filing.
What is a hazardous materials management plan (HMMP)?
A plan the fire code official may require under the International Fire Code. Section 5001.5.1 calls for a facility site plan showing, among other things, access to each storage and use area, emergency equipment, tanks, the hazard classes in each area, control areas and emergency exits. A Tier II site map drawn to that list can serve both purposes.
Do Group H occupancies have to file in Gilbert?
Yes. The regulation says all facilities designated as a Group H occupancy are required to electronically file.
How do I list a product such as bleach?
By its chemical name, not the product name. The regulation gives bleach as the example: it is filed as sodium hypochlorite solution.
Who do I ask at the Town of Gilbert?
Gilbert Fire Prevention Division, 85 E Civic Center Drive, Gilbert, AZ 85296, 480-503-6350, fireprevention@gilbertaz.gov.
Sources, checked 15 November 2026: ADEQ Tier II Reporting page; ADEQ “EPCRA & Tier II Reporting” presentation, January 2025; 40 CFR 370.10(b)(2); Town of Gilbert Fire Prevention Regulation 18-5003.4.1 (revised 3/6/2024). RevealBuilt draws the map. It is not a regulator and does not decide what you must report. For that, ask your Tier II preparer or ADEQ’s Tier II line at 602-771-0397 or tier2@azdeq.gov.